CONSTRUCTION
Enclosure: PA glass fiber reinforced polyamide, color – black
Cover: PA glass fiber reinforced polyamide with integrated thermoplastic elastomer gasket,
closes with four M5 stainless steel screws.
| Apparatus category: | II 2GD |
| Explosion protection: | Ex eb IIC T6 Gb Ex ia/ib IIC T6 Gb Ex tb IIIC T80°C Db |
| Enviroment temperature: | -20ºC ≤ Ta ≤ +50ºC, Ta ≤ +70ºC for Exi [ATEX] -50ºC ≤ Ta ≤ +50ºC [EAC] |
| Degree of protection: | IP66 |
| Rated insulation voltage: | 630 VAC
60 V (Exi) |
Zone 1,2,21,22
● Enclosures made of PA glass fiber reinforced polyamide
● The cover screws and all other external metal parts are made of stainless steel (AISI 316L)
● Equipped with terminals up to 6mm2
● Pillar (mantle) terminals